Traditional Culture Encyclopedia - Hotel accommodation - What are the hotel's requirements for fire exits?

What are the hotel's requirements for fire exits?

5.3 Safe evacuation of civil buildings

5.3. 1 Safety exits of civil buildings shall be distributed. The horizontal distance between the nearest edge of two adjacent exits of each fire zone and each floor of the fire zone should not be less than 5.0m

5.3.2 The number of fire exits in each fire zone and each floor in a fire zone of public buildings shall be calculated and determined, and shall not be less than 2. When one of the following conditions is met, emergency exits or evacuation stairs can be set:

1 Single-storey public buildings with a building area of 200m2 or less and no more than 50 people, except nurseries and kindergartens;

Besides hospitals, sanatoriums, buildings for the elderly and nurseries, children's rooms and playgrounds in kindergartens, etc. , the second and third floors of public buildings meet the requirements in Table 5.3.2.

Table 5.3.2 Conditional fire resistance rating of public buildings 1 exit.

Maximum number of floors

Maximum construction area of each floor (m2)

number of people

Primary and secondary

Third layer

500

The sum of the number of people in the second and third floors shall not exceed 100.

Three levels

Third layer

200

The sum of the number of people in the second and third floors shall not exceed 50.

Totally good.

2 layer

200

There are no more than 30 people on the second floor.

5.3.3 Buildings for the elderly, nurseries, children's rooms in kindergartens, children's play halls and other places for children's activities should be set in independent buildings. When it must be installed in other civil buildings, it is advisable to set up independent safety exits, which shall comply with the provisions of Article 5. 1.7 of this specification.

5.3.4 When there are not less than two evacuation staircases in public buildings with Grade I and II fire resistance, the number of floors in the local elevated part of the top floor is not more than two, and the total number of people is not more than 50, and the construction area of each floor is less than or equal to 200m2, 1 evacuation staircases directly communicating with the stairwell of the lower main building can be set in the local elevated part, but at least 1 other pedestrian floors should be set.