Traditional Culture Encyclopedia - Hotel accommodation - The hotel is 600 meters away from the transformer. The electricity consumption is about 70 kilowatts. How much 3-phase 4-wire aluminum underground wire should be used? How to calculate it? Is there a
The hotel is 600 meters away from the transformer. The electricity consumption is about 70 kilowatts. How much 3-phase 4-wire aluminum underground wire should be used? How to calculate it? Is there a
The hotel is 600 meters away from the transformer. The electricity consumption is about 70 kilowatts. How much 3-phase 4-wire aluminum underground wire should be used? How to calculate it? Is there a formula?
The power consumption is about 70 kilowatts, and the working current is about: I=70/(1.732*0.38*0.8)=133A
The aluminum conductor should not be less than: S=133/2 =66.5 square millimeters
According to the wire specification, aluminum conductor 3*71*35 should be used
This seems to be possible, but the power supply radius is generally considered within 500M.
And since you are a hotel, there are many single-phase electrical appliances, such as lighting fixtures.
It is recommended that you use YJLV22-4*120 cable.
- Previous article:Four-star hotel bathroom management!
- Next article:Are the comments on the hotel reservation website true?
- Related articles
- How to design a homestay
- How about Hangzhou Xinkaiyuan Hotel Co., Ltd.?
- My daughter wouldn't let my mother travel with her backpack, and she said it was old-fashioned. Is backpacking really old-fashioned?
- How far is it from Zhenjiang Railway Station to Lijing Hotel?
- Chairman of Zhongzhou International Group Zhongzhou International Group
- How many star hotels is Orange Hotel?
- Common sense of tourism equipment
- Where is the Kiwifruit Base in Wenzhou-Recommended Picking Place
- How to get to the Governor's Office of Xiyu Hotel by bus?
- What's the room number of Zhaoping Vienna Hotel?