Traditional Culture Encyclopedia - Hotel accommodation - Fire fighting system and equipment maintenance system
Fire fighting system and equipment maintenance system
Second, the centralized management department is responsible for the daily management of fire-fighting facilities and equipment, and each department is responsible for the intact and effective situation of fire-fighting facilities and equipment within its scope of responsibility, and determines the specific responsible person.
Third, sign a maintenance contract with the unit that has the ability to maintain the building fire protection facilities, conduct maintenance once a month, issue a maintenance report, and conduct functional testing at least once a year to ensure its normal use.
Four, automatic fire alarm system detector cleaning after 2 years, after cleaning once every 3 years.
Five, fire extinguishers at least once a year to entrust the maintenance unit to check all fire extinguishers. All used and failed fire extinguishers must be inspected by the maintenance unit, replaced with damaged parts, and refilled with fire extinguishing agent and driving gas. The fire extinguisher scrapping system must be implemented, fire extinguishers that have exceeded their service life must be forcibly scrapped, and new fire extinguishers should be selected. Establish a fire extinguisher file, recording the configuration type, quantity, installation location, inspection and maintenance unit (personnel), and chemical replacement time.
Six, every two years to conduct a comprehensive inspection of the fire pool, fire water tank, repair defects and anti-corrosion treatment; The water supply capacity of water source is determined once a year; Conduct a water discharge test on the alarm valve once every quarter, and overhaul the pipeline control valve; The water flow indicator is detected by the terminal water detection device every two months; Conduct a comprehensive inspection on the water level and pressure of fire-fighting pool, fire-fighting water tank and fire-fighting air pressure water supply equipment every month; The fire pump starts running once a month, and the simulated automatic control starts running once; The internal combustion engine drives the fire pump to run once a week; Check the solenoid valve once a month and start the experiment; Check the appearance of all nozzles once a month; Outdoor fire hydrants, indoor fire hydrants and water pump adapters shall be inspected once a month. The above inspection shall be recorded in the duty record of the fire control room.
Seven, are not allowed to use fire alarm, manual alarm button, fire jack telephone, automatic sprinkler alarm valve, fire shutter manual switch, etc. , found that the damage should be reported in time.
- Previous article:What is the landmark building in Quanzhou City?
- Next article:Is it appropriate to tell girls in the hotel room?
- Related articles
- How many stars does Jiaxing Boya Garden Hotel have?
- How about Yijia International? OK? Is it worth buying?
- List of big-name lipstick brands (what brand of lipstick is easy to rank)
- "Salon in 2065438+02" ¡¬ Overlooking the old town of Guangzhou in Aiqun Building.
- What does the parent-child cabin mean?
- Which is better, Old Pinghu Hotel or Family Hotel?
- Which hotels in Lu 'an Development Zone need to pay in advance for online booking? How to check in after arriving at the hotel?
- What's the discount for Hokkaido Fuxing? 20 18 what are the benefits of Hokkaido tourism?
- Ctrip.com official website Telephone Ctrip.com official website Telephone Manual Service
- Shuttle schedule of Kangding airport