Is it legal to have a boiler next to a hotel in a community?
The boiler room design specification GB50041-2008
The legality cannot be assessed, but the design of the boiler room is standardized. See if you can refer to it.
As follows:
Boiler room design specification GB50041-2008
Boiler room layout
4.1
Location Selection
4.1.1
The selection of the location of the boiler room should be determined based on the analysis of the following factors:
1. It should be close to areas with relatively concentrated heat loads. And the layout of the heating pipes and outdoor pipe network should be technically and economically reasonable;
2 It should be convenient for fuel storage and transportation and ash and slag discharge, and it should be convenient for the flow of people and the transportation of fuel and ash. Logistics should be separated;
3 There should be room for expansion at the expansion end;
4 It should be conducive to natural ventilation and lighting;
5 It should be located in a place with good geological conditions Area;
6 It should be conducive to reducing the impact of smoke, harmful gases, noise and ash on residential areas and major environmental protection areas. Boiler rooms that operate throughout the year should be located on the upwind side of the overall minimum frequency wind direction. , the boiler room for seasonal operation should be located on the downwind side of the maximum frequency wind direction in that season, and should meet the requirements set forth in the environmental impact assessment report;
7 Coal-fired boiler rooms and gas generating stations should be arranged In the same area;
8 It should be conducive to the recovery of condensate water;
9 The regional boiler room should still comply with the requirements of the city's overall planning and regional heating planning;
10 The location of the boiler room of an enterprise producing flammable and explosive goods,
in addition to meeting the above requirements of this article,
should also comply with relevant professional specifications.
4.1.2
The boiler room should be an independent building.
4.1.3
When the boiler room is connected to or installed inside other buildings, it is strictly prohibited to set it up or down the upper or lower floors of crowded places or important departments. Adjacent locations and on both sides of main passages and evacuation exits. And should be installed on the first floor or basement level near the exterior wall of the building.
4.1.4
It is not appropriate to install a boiler room in a residential building.
4.1.5
Boiler rooms using pulverized coal boilers should not be located in residential areas, scenic spots and other major environmental protection areas.
4.1.6
Boiler rooms using circulating fluidized bed boilers should not be located in residential areas.
4.2
Arrangement of buildings, structures and sites
4.2.1
Each building, structure and site in the independent boiler room area The floor plan and spatial combination of the structure should be compact and reasonable, with clear functional divisions, simple and coordinated construction, and meet the requirements of smooth process flow, safe operation, convenient transportation, and installation and maintenance.
4.2.2
The pre-plant area planning of a new regional boiler room should be coordinated with the regional planning. The main building and ancillary buildings of the boiler room should be arranged as a whole. The main facade of the building in the boiler room area should face the main road, and the overall layout should be reasonable and beautiful.
4.2.3
The architectural form and layout of industrial boiler rooms should be coordinated with the architectural style of the enterprise; civil boiler rooms and regional boiler rooms
The architectural form and layout should be coordinated with the architectural style of the city (region) where it is located.
4.2.4
The layout of each building, structure and site in the boiler room area should make full use of the terrain to minimize the amount of excavation and filling and discharge
The water flows smoothly, and water flow into the basement and pipe trenches should be prevented.
4.2.5
The distance between boiler rooms, coal yards, ash yards, oil storage tanks, gas pressure regulating stations and other buildings and structures should be
It complies with the current national standards "Code for Fire Protection Design of Buildings" GB50016, "Code for Urban Gas Design" GB50028 and relevant standards, and meets the requirements for installation, operation and maintenance.
4.2.6
The layout of the coal transportation system should make use of the terrain to make the lifting height small and the transportation distance short. Coal yards and ash yards should be located on the upwind side of major buildings
with the lowest frequency of wind throughout the year.
4.2.7
The elevation of the indoor bottom floor of the boiler room building and the elevation of the top surface of the structure foundation should be 0.15m or more higher than the outdoor floor or surrounding floors. The floor elevation of the boiler room and the auxiliary room on the same floor should be consistent.
- Related articles
- How about Xi Antungen Trading Co., Ltd.
- What does Mr. Song Yu Ning want from Lori? Does Mr. Song want Yu Ning and Lori to get back together?
- What hotels are there at the intersection of Dayun Road in Qixian County?
- How about Sunshine (China) Holiday Chain Group Co., Ltd.
- One-day tour of go on road trip near Tangshan.
- Can you provide detailed information about the specific accommodation of Tibet tourism, preferably with the phone number of the hotel?
- A poem introducing Chinese
- Are there any hotels or guesthouses near Guangzhou Gymnasium? It is best to walk within 10 minutes.
- Top ten most luxurious hotels in the world
- Li Yiru character introduction