Traditional Culture Encyclopedia - Hotel reservation - Can the shops on the first floor of the hotel use gas?

Can the shops on the first floor of the hotel use gas?

You can't. It is expressly stipulated that there are residents upstairs, and liquefied gas tanks cannot be used for catering on the first floor.

Three. Requirements for gas use places

(a) the use of urban pipeline gas supply, gas pressure regulation, metering, pipelines, valves and other facilities should comply with the "Code for Design of Urban Gas" (GB50028).

(2) Gas-using places shall be equipped with combustible gas concentration detection and alarm devices in accordance with relevant regulations, which shall be regularly detected and recorded to ensure that they are in a sensitive and effective state, and equipped with dry powder fire extinguishers and other fire-fighting equipment in accordance with standards.

(3) Steel cylinders placed in gas-using places must be connected with gas burning appliances in the form of single bottles, and the horizontal clear distance from gas burning appliances should not be less than 0.5m..

(4) Gas-using places must have good ventilation conditions, set up mechanical air supply and exhaust devices that meet the ventilation requirements, and set up facilities to effectively eliminate burning smoke above gas appliance.

(five) it is strictly forbidden to place liquefied petroleum gas cylinders in restaurants.

Four, gas equipment and facilities requirements

(a) gas appliances, gas cylinders, connecting pipes and other accessories should meet the product quality requirements and product technical requirements of the current national standards, and it is strictly forbidden to use fake and shoddy products.

(2) Before and after using gas, it is necessary to check whether the gas appliances are in good condition and whether the gas switch is reliable. When problems are found, it is necessary to promptly report the gas burning appliances installation and maintenance enterprises with corresponding qualifications for maintenance or replacement.

(3) Within the effective service period of gas cylinders, the contents of inspection marks shall be complete and clear, and gas cylinders without warning labels, filling marks, expired or scrapped shall not be used.

(4) The normal service life of pressure reducer for liquefied petroleum gas cylinders is 5 years, and the normal service life of sealing ring is 3 years. When it expires or problems are found, it should be replaced immediately and recorded.

(five) the supply of multiple gas cookers, steel pipe laying should be adopted; When the main gas pipeline is connected with multiple gas stoves, stainless steel bellows with double thread connection should be used. The length of stainless steel bellows shall not exceed 2m, and there is no interface in the middle; Stainless steel bellows shall not pass through walls, floors, ceilings, doors and windows.

(6) The connection between a single gas cylinder and a single gas cooker shall be made of stainless steel bellows with double threads; When using oil-resistant rubber hose, both ends of the connection should be fastened with clamps, and the length of the hose should be controlled between 1.2m ~ 2.0m, with no joint in the middle. It is forbidden to set a three-way shunt on the hose; Rubber hoses should be replaced every two years. When they are out of date or aging, cracking and corrosion are found, they should be replaced in time and a replacement record should be established.