Excuse me, what requirements should the hotel emergency lighting meet?

Please refer to the code for fire protection of building design.

1 1.3.2 The illuminance of fire emergency lighting in the building shall meet the following requirements:

1 The minimum horizontal illumination on the ground of the evacuation walkway should not be less than 0.5lx;;

2 The minimum horizontal illumination on the ground in crowded places should not be lower than1.0lx; ;

3 The minimum horizontal illumination on the stairwell floor should not be less than 5.0lx;;

4 The fire emergency lighting in the fire control room, fire water pump room, self-provided generator room, power distribution room, smoke control room and other rooms that still need to work normally in case of fire should still ensure the illumination at normal lighting time.