A public building with a building height of less than 24m has a baking factory on the first floor and offices on the second and third floors. Is it necessary to make a fire sprinkler system?
8.5 Location of automatic fire extinguishing system
8.5. 1 The following places shall be equipped with automatic fire extinguishing systems. Unless it is not suitable for waterproof or fire extinguishing and otherwise specified in this specification, automatic sprinkler system shall be adopted:
1 50000 spindle and above cotton mill opening and cleaning workshop; Classification carding workshop of linen mills with 5000 spindles and above; Dry, and screening match factory part; Pre-production, molding, slicing and embossing of foam plastic factory; Woodworking workshop covering an area of more than 1500m2; /kloc-Single-storey and multi-storey factories for shoes, clothing, toys and electronics with a total construction area of more than 0/500m2 or 3000m2; High-rise class C factory building; The preparation part of the aircraft engine test bed; Class C underground workshop with a building area of more than 500m2;
2 warehouses for cotton, wool, silk, hemp, chemical fiber, fur and its products with an area greater than 1000m2; Match warehouses with an area of over 600 square meters each; An empty mail bag warehouse with a construction area of more than 500 square meters in the postal building; Underground warehouse of combustible materials with a building area of more than 500m2; Elevated warehouses and high-rise warehouses for inflammable and flame-retardant articles (except cold storage);
3./kloc-a special, first-class or other theater with more than 0/500 seats; A hall or auditorium with more than 2000 seats; A gymnasium with more than 3,000 seats; Lounge and equipment room for indoor staff in sports venues with more than 5,000 people;
4. Exhibition buildings, shops and hotel buildings with a building area of more than 1500m2 or a total building area of more than 3000m2, as well as ward buildings, outpatient buildings and operating departments with the same building scale in hospitals; Underground shops with a building area of more than 500m2;
5. A central air-conditioning system with return air pipes (pipes) and an office building with a total construction area of more than 3000m2;
6 Underground, semi-underground, or more than four floors above the ground, or more than one, two or three floors of buildings, and the construction area of any floor is more than 300m2 (except swimming places);
7 libraries with more than 500,000 books.
8.5.2 The water curtain system shall be set in the following positions:
1 large class, Class A class or other classes with more than 1500 seats, the stage entrance of an auditorium or auditorium with more than 2000 seats, and the doors and windows of the side platform and backstage connected to the stage;
2. Local openings that cannot be set due to fire partitions such as firewalls;
3 the upper part of the fire shutter or fire curtain that needs cooling protection.
8.5.3 The following places shall be equipped with rain shower system:
1 match factory potassium chlorate crushing plant; A factory building that produces and uses nitrocellulose, spray-painted cotton, collodion, celluloid film and nitrocellulose with a building area greater than 100m2;
2 warehouses of nitrocellulose, spray-painted cotton, collodion, celluloid film and nitrocellulose with a building area of more than 60 square meters or a storage capacity of more than 2t;
The bottling room and actual bottle warehouse of the LPG storage and distribution station where more than 3,000 bottles are bottled on the 3rd;
4.65,438+0,500-seat grand theater, first-class theater or other theaters and 2,000-seat auditorium;
5. Studios with a building area of over 400㎡ and film studios with a building area of over 500㎡;
6. Inspection parts for blank rolling, slicing, ball grinding and ball distribution in table tennis factory.
8.5.4 The following places shall be equipped with automatic fire extinguishing system and water spray fire extinguishing system:
1 Oil-immersed power transformers in factories and mines with a capacity of 40MVA or above, oil-immersed power transformers in oil-immersed power plants with a capacity of 90MVA or above, or oil-immersed power transformers in independent substations with a capacity of 125MVA or above;
2. Aircraft engine test-bed test site.
8.5.5 The following places shall be equipped with automatic fire extinguishing system and gas fire extinguishing system:
1 Microwave room, meter room, meter room, power distribution room and uninterruptible power supply (UPS) room of national, provincial or city radio and television transmission towers with a population of more than 1 10,000;
2. International Telecommunication Bureau, regional center, provincial center, regional center 1 10,000 long-distance program-controlled exchange room, control room and signaling transfer point room;
The SPC exchange room, control room and signaling transfer point room of the local telephone tandem office with more than 20,000 lines and the local telephone terminal office with more than 60,000 lines;
Communication rooms and control rooms of public security, disaster prevention and electric power dispatching command centers at or above the bureau level at the central and provincial levels;
5. Recording magnetic (paper) media library, located in the computer room and basic workshop, with a construction area of140m2;
Audio-visual products warehouses with a building area of not less than 120m2 in the central and provincial radio and television centers;
7. More than 6,543,800+0,000 volumes are specially collected at the national, provincial or library level; Treasures and non-paper files of the central and provincial archives; Treasures warehouse of large and medium-sized museums; First-class paper and silk cultural relics showroom;
8 Other special and important equipment rooms.
Note: When there is a standby host and a standby recording magnetic (paper) medium, which are located in different buildings or different fire zones of the same building, the pre-action automatic sprinkler system can also be used in the parts specified in paragraph 5 of this article.
8.5.6 The locations of foam fire extinguishing systems such as Class A, Class B and Class C liquid storage tanks shall comply with the provisions of current national standards GB50074, GB50 160 and GB50 183.
8.5.7 In crowded places such as exhibition halls and gymnasium audience halls with a building area of more than 3000m2, and Class C workshops with a building area of more than 5000m2 that cannot use automatic sprinkler systems, fixed fire monitors and other fire extinguishing systems should be set up.
8.5.8 For catering establishments with a business area of more than 500m2 in public buildings, automatic fire extinguishing devices should be installed in the cooking hood and cooking parts in the cooking operation room, and automatic emergency cut-off devices should be installed on gas or oil pipelines.
- Related articles
- Appreciation of Hu Jianbo's Song of Fu Ren
- The prologue of the company's celebration
- What will be collected the day after tomorrow 18, what will be collected separately, and where will it be collected?
- Why do many goods have cylindrical packaging?
- If you do these 6 points, you can easily get into debt
- Shenzhen Aidu wedding photography
- How to detect whether your pelvis leans forward?
- How to burn high-definition movies completely on vcd with sound and shadow
- What does photography often mean by exposure?
- An all-rounder that can suck and drag, looking for the cordless vacuum cleaner V12 experience